Sun Xtender Technical Briefing - SOC, OCV, & DOD

TECHNICAL BRIEF


Subject: Battery Load Voltage vs. Depth of Discharge (DOD) Table
Battery State of Charge (SOC) vs. Open Circuit Voltage (OCV) Table

Battery Load Voltage vs. DOD

Below are listed the one hour, 8 hour, 20 hour and 100 hour load voltages during the discharge cycle from full charge to 100% discharge to 1.75V/cell or 10.5V (6 cells) at 25°C (77°F).

DOD (%) 1 hr. Rate 8 hr. Rate 20 hr. Rate 100 hr. Rate
0 14.20 14.20 14.20 14.20
<1 N/A 12.85 12.91 13.45
10 12.51 12.72 12.80 13.16
20 12.42 12.59 12.66 12.91
30 12.32 12.48 12.52 12.75
40 12.20 12.35 12.38 12.60
50 12.06 12.18 12.22 12.43
60 11.90 12.00 12.06 12.25
70 11.75 11.87 11.90 12.03
80 11.58 11.66 11.70 11.81
90 11.31 11.40 11.42 11.52
100 10.50 10.50 10.50 10.50


Please note that these voltages are averages and will vary slightly from battery to battery even of the same rating. They are however a good indicator of state of charge and can be used when setting low voltage alarms or disconnects for a Concorde AGM battery. Other battery types or manufacturers voltage vs. DOD may be substantially different.

Also, the data is for newer batteries with relatively few cycles. An older battery will measure a lower voltage for a given state of charge.

The 0% DOD voltage is the voltage measured upon removal of the battery from charge with no load applied. This voltage can vary depending on the set point of the charging unit.

SOC (%) vs. OCV

Another method to estimate the State of Charge (SOC) of the battery is by measuring its Open Circuit Voltage (OCV). This measurement should be made after the battery has been at rest for two to three hours with the battery disconnected from its charging source and load. The voltage is listed as Volts/Cell and for a 12V (6 cell) battery at 25°C (77°F).
State of Charge (%) OCV/Cell OCV/12V Battery
100 2.13 or greater 12.8 or greater
80 2.10 12.6
60 2.05 12.3
40 2.00 12.0
20 1.97 11.8
0 1.93 or less 11.6 or less


These voltage levels are approximate and give an indication of the state of charge of a battery at rest. As the battery ages these voltage measurements will be lower.

November 12, 1999 (EM)



The data/information contained in the Sun Xtender official website has been reviewed and approved for general release on the basis that these documents contain no export-controlled information.
Home Page | Sun Xtender Batteries | Battery Applications | Sun Xtender 2V / 6V / 12V Battery Series Battery Distributors |
MSDS | About Sun Xtender | Contact Sun Xtender | Solar Energy Sitemap Press Releases |
AS 9100 REV. B:2004 & ISO 9001:2000 (pdf) | Renewable Energy Directory | Employment Opportunities

All Rights Reserved. © 1996-2008
Built by Broomfield Designers Hosted at Broomfield-Designers.com


Sun Xtender Battery Produces the Highest Quality Solar Batteries,
Renewable Energy Storage Batteries, Photovoltaic Batteries, & AGM Batteries